Page 168 of 456 Configuring the system monitor
NN43021-310 Standard 02.01 December 2007
Cabling the Candeo
There are eight configurable Candeo output ports for output alarms. Each
output port can use one of the following three contact types: normally open,
normally closed, and common. Large Systems use normally closed contacts.
Common contacts connect to the Candeo battery return bus. The connector
strip J8 is used for all output connections and is removable from the System
Manager for ease of wiring. Ensure that pin 1 is in the correct orientation for
wiring when strip has been removed.
Configuring the alarm ports
Follow the steps in Procedure 17 to configure the alarm ports.
Table 16
Cable lengths
Cable Length
NT8D46AV 9.75 m (32 ft)
NT8D46BV 19.5 m (64 ft)
NT8D46CV 30 m (100 ft)
Table 17
Alarm configuration – NT8D46xx
Label Colour
Candeo
alarm port
Candeo
J8 connector
Candeo
configuration
DCON0 Black Port 1 J8-1 Normally Closed Loss of AC power
DCON1* Red Port 2 J8-1 Normally closed Major alarms
DCON2* White Port 2 J8-4 Normally closed Major alarms
DDON3* Green Port 2 J8-4 Normally closed Major alarms
ALARM Orange Port 3 J8-7 Normally Closed Low float
* Twist red, white and green together and connect to port 2 as Major
Jumper together and connect to battery return bus. J8-2,5,8