Nortel-networks Circuit Card Manual de usuario Pagina 231

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 908
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 230
NT5D11 and NT5D14 Lineside T1 Interface cards Page 231 of 906
Circuit Card Description and Installation
Q Quit
Logs the terminal user out. If multiple lineside T1 cards share a single terminal,
logout after using the MMI. Because of the shared daisy-chained link, if a lineside
T1 card is logged in, it occupies the bus and no other lineside T1 cards are able to
notify the MMI of alarms.
S A Set Alarm parameters
Alarm parameters include the allowable bit errors per second threshold and alarm
duration.
S C Set Clearing
Sets the alarm self-clearing function to either enable or disable
.
S D Set Date
Sets date or verifies current date.
S T Set time
Sets time or verifies current time.
T x Test
Initiates the T1 carrier test function. To terminate a test in process, enter the
STOP TEST (S) command at any time.
Table 88
MMI commands and command sets (Part 3 of 3)
Command Description
Vista de pagina 230
1 2 ... 226 227 228 229 230 231 232 233 234 235 236 ... 907 908

Comentarios a estos manuales

Sin comentarios