Page 236 of 906 NT5D11 and NT5D14 Lineside T1 Interface cards
553-3001-211 Standard 3.00 August 2005
The “Disable Self-Clearing” option causes the system to continue the alarm
condition until the Clear Alarm (C A) command set is entered. Line
processing and the yellow alarm indication to the CPE is terminated as soon
as the alarm condition clears, even if “Disable Self-Clearing” is set.
Display Configuration
The Display Configuration (D C) command set displays the various
configuration settings established for the lineside T1 card. Entering the
Display Configuration (D C) command set causes a screen similar to the
following to appear:
LTI S/N 1103 Software Version 1.01 3/03/95 1:50
Alarms Enabled: YES Self Clearing Enabled: YES
Alarm Level 1 threshold value: E-7 Threshold duration
(in seconds): 10
Alarm Level 2 threshold value: E-5 Threshold duration
(in seconds): 1
Frame slips alarm level threshold: 5 Threshold duration
(in hours): 2
Current dip switch S1 settings (S1..S8) On Off Off On Off
Off Off On
Current dip switch S2 settings (S1..S8) On Off On Off Off
Off On Off
Alarm operation and reporting
The MMI monitors the T1 link according to the parameters established
through the Set Alarm command set for the following conditions:
Excessive bit error rate
Frame slip errors
Out of frame condition
Loss of signal condition
Blue alarm (AIS) condition