Page 114 of 456 Installing DC power
NN43021-310 Standard 02.01 December 2007
2 Connect the other end of the cable to the FG collector with a parallel tap
connector, as shown in the left side illustration of Figure 37 on page 114.
Continue with step 4.
3 Connect the other end of the cable to the nearest floor ground bar (FGB),
which in some sites may be the building principal ground (BPG), as shown
in the right side illustration of Figure 37 on page 114.
4 Repeat step 1 for any other frames as applicable.
5 Secure the cables as required and use an identification tag with the
wording
PWR PLT FG to identify the cables at the BPG or FGB
connection.
End of Procedure
Figure 37
Typical installation of the power system frame ground lead
553-AAA1515
Candeo power
system
framework
Candeo power
system
framework