Preparing for installation Page 57 of 456
Communication Server 1000M and Meridian 1 Large System Installation and Commissioning
2 Vertically on the sides of the module
3 Vertically in the corner channels in the rear of the module (shielded
cables only)
Nortel recommends that you use the 90° connector end of the cable to route
the cable through a module or cabinet instead of the 180° end, since some
openings are small (see Figures 14 and 15). Furthermore, Nortel recommends
that you route cables top-to-bottom so gravity will ease installation.
Figure 14
90° cable connector
CAUTION
Damage to Equipment
Cables must be routed as perpendicular as possible
to any nearby power cables. Avoid routing cables
near power cables if alternate routing is available. (At
the rear of the module, cables routed between the I/O
panel and the rear cover can be parallel to the power
cables because the panel provides EMI shielding.)
553-749