
Planning and designating a Main Distribution Frame Page 135 of 456
Communication Server 1000M and Meridian 1 Large System Installation and Commissioning
Procedure 11
Installing the BIX cross-connect terminal
1 Refer to the equipment layout plan to determine where to place the
cross-connect terminal.
2 Lay out the terminal blocks as shown in Figure 50 on page 137.
3 Attach labels on the cross-connect terminal to indicate the terminal blocks
assigned to the following:
• 25-pair cables from the system
•AUX wiring
• Power Failure Transfer Units (PFTU)
• Telephones and consoles
•Trunks
• Miscellaneous equipment
End of Procedure
Figure 48
Typical BIX cross-connect terminal layout
Standard backplane cabling: White background
A
0
A
0
SP
T R T RT RT R T R T R T R T R T R T R T R T R T R T R T R
71523456 8910111213141
0
SP
0
SP
T R T RT RT R T R T R T R T R T R T R T R T R T R T R T R
71523456 8910111213141
B B
1
0
T R T R T R T R T R T R T R
7234561
553-3102
8
SP
T R T RT R T R T R T R T R T R T R T R T R T R T R T R
15
7
10 11 12 13 14 0 1 2 3 4 5 69
C C
3
8
T R T R T R T R T R T R T R
1510 11 12 13 149
T R
T R
2
Expanded backplane cabling: White background
A
A
SP
SP
B
SP
C C
0
T R T RT RT R T R T R T R T R T R T R T R T R T R T R T R
71523456 8 910111213141
T R
T R T R T R T R T R T R T R T R
16 17 18 19 20 21 22 23
B
0
T R T RT RT R T R T R T R T R T R T R T R T R T R T R T R
71523456 8 910111213141
T R
T R T R T R T R T R T R T R T R
16 17 18 19 20 21 22 23
0
T R T RT RT R T R T R T R T R T R T R T R T R T R T R T R
7152345 6 8 910111213141
T R
T R T R T R T R T R T R T R T R
16 17 18 19 20 21 22 23
Comentarios a estos manuales